한영넉스

Solid State Relay > HSR-2E series : HANYOUNG NUX
HSR-2E series Single-phase 2-wire control overcurrent sensing solid-state relay
- Accurate under/overload detection in On/Off cycle control situations.
- True RMS current measurement
- Display of operation status, output status, alarm LED
- Medium alarm, light alarm relay contact output
- Integrated heat sink
- Detection of TRIAC SHORT, load disconnection, overcurrent, and undercurrent
- 2-wire cutoff method (simultaneous control of two lines of single phase)
- Alarm record function (type of alarm and max current of 20ea)
- Application of bimetal at 60℃, 80℃

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

Model

HSR-2E10LZ

HSR-2E20LZ

HSR-2E30LZ

HSR-2E10HZ

HSR-2E20HZ

HSR-2E30HZ

Output

Load voltage range

24 - 240 V a.c.

24 - 480 V a.c.

Peak voltage

1,200 V

Surge current

400 A

Rated load current

10 A

20 A

30 A

Leakage current

Max. 15 mA

Voltage Drop at

ON-state

Max. 1.6 V (R.M.S)

Input

control

signal

Voltage (V)

4 ~ 32 V d.c. (consumption current 4 ~ 14 mA d.c.)

circuit power

22 ~ 25 V .d.c.

OFF-state voltage

Max. 1 V

current consumption

Max. 40 mA d.c.

Contact

Rating

Relay Contact

Alarm1, Alarm2, 0.5 A, 125 V a.c. / 0.3 A, 110 V d.c. / 1 A, 30 V d.c.

BI METAL Contact

▪ Max. 60 ℃, 80 ℃, 2.5 A, 48 V d.c.

▪ Max. 60 ℃, 80 ℃, 0.5 A, 240 V a.c.

Response Time

1/2 Cycle + 1 ms max. 8.3 msec (60 Hz)

Insulation resistance

500 V d.c., 100 MΩ

Dielectric strength

2,500 V a.c. (60 ㎐ for one minute)

Rated impulse withstand voltage

(Uimp)

2,500 V

Vibration resistance

10 - 55 Hz,   single amplitude : 1.5 mm,   Each X · Y · Z axis for 2 hours

Shock resistance

1,000 m/s²,   X · Y · Z each axis 3 time

Storage temperature

-30 ~ 90 ℃

Ambient temperature

-20 ~ 50 ℃ (No Condensation)

Ambient humidity

30 ~ 85 % RH

Applied Load

Resistive load

Mounting Specification

DIN Rail & Screw

Certification

인증마크

Weight (g) with heatsink box

Approx. 350 g

Approx. 542 g

Approx. 700 g

▍Suffix code

Model

Code

Content

HSR

Single-phase 2-wire control overcurrent sensing solid-state relay

Rated load

current

10

 

 

10 A

20

 

 

20 A

30

 

 

30 A

Rated load voltage

L

 

24 - 240 V a.c.

H

 

24 - 480 V a.c.

Operation method

Z

Zero cross switching

▍Dimension

[Unit : ㎜]

■ HSR-2E10□□

Dimension

■ HSR-2E20□□

Dimension

■ HSR-2E30□□

Dimension