▍Specification

Classification

VX2

VX3

VX4

VX7

VX9

Input

Thermocouple

K, J, E, T, R, B, S, L, N, U, W, PLII

Reference junction

compen sation accuracy

± 1.5 ℃ (within -10 ~ 50 ℃)

RTD

JPT100, PT100

Allowable line

resistance

Each 3 wire within 10 Ω

(but the resistance among 3 lines should be same)

DC voltage / current

1 ~ 5 V (4 ~ 20 mA), 0 ~ 5 V, 0 ~ 10 V, 0 ~ 50 mV, 0 ~ 100 mV

Sampling cycle

50 ms

Control

output

Relay output

▪Rated switching capacity : 5 A 240 V a.c., 5 A 30 V d.c.   ▪Max. switching power : 750 VA, 90 W

▪Max. switching voltage : 240 V a.c., 110 V d.c.   ▪Max. switching current : 5 A

▪Mechanical life : 20 million times (at 180 CPM)

AC voltage type voltage

pulse output

12 V d.c. ± 1 V d.c. pulse voltage (load resistance min. 600 Ω)

DC voltage type voltage

pulse output

12 - 15 V d.c. pulse voltage (load resistance min. 600 Ω)

Current output

4~20 mA ± 0.2 % of FS ± 1 digit, load resistance : max. 600 Ω

Control

Control type

ON/OFF, PID control, 2DOF PID control

Output operation

Reverse action, direct action

Memory

Non-volatile

memory life

▪EEPROM unlocked : when setting E2P.L : OFF in G.SET group (EEPROM life : 1 million times write guaranteed)

▪EEPROM locked : when setting E2P.L : ON in G.SET group (store in RAM)

Display

part

(H*W)mm

Display method

Wide viewing angle LCD

PV character

20.5 x 6.9

19.7 x 7.2

15.2 x 6.8

19.8 x 9.3

29.0 x 13.6

SV character

12.8 x5.9

10.7 x4.7

7.4 x3.9

10.2 x4.9

15.0 x 7.2

MV character

9.3 x 4.4

7.3 x 3.5

7.4 x 3.9

7.5 x 3.3

11.0 x 4.8

USB

Loader

Communication

method

USB 2.0

Protocol

▪Protocol : PC-LINK    ▪Baudrate : 38400 bps    ▪Start bit : 1 bit

▪Data bit : 8 bit    ▪Parity bit : None    ▪Stop bit : 1 bit

Communication

distance

Within 5 m

Option

Sub output

▪Relay 1 ~ 4 outputs    ▪rated switching capacity : 5A 240 V a.c.,  5 A 30 V d.c.

Digital input

▪2 points or 4 point

▪Contact input ON : 1 KΩ max., OFF: 100 KΩ min.

▪Non-contact input ON : 1.5 V max., OFF: 0.1 mA max.

▪Current Flow : approx. 2 mA per contact,

▪Voltage at open : Approx. 5 V d.c.

Retransmission

output

▪1 output   ▪4 ~ 20 mA ± 0.2 % of FS ± 1 digit

▪load resistance : max. 600 Ω

Remote input

▪1 input ▪4 ~ 20 mA (1 ~ 5 V)

Current

detection

input

▪1 input or 2 inputs ▪0.0 - 50.0 A ▪CT-70 current transformer (sold separately)

RS-485

Communic

method

▪EIA RS485 standard   ▪2-wire half-duplex

Max.

connections

31 (address setting 1~99 available)

Communic

sequence

No sequence

Communic

distance

Within 1.2 ㎞

Communic

speed

4800, 9600, 14400, 19200, 38400, 57600 bps

bit

▪Start bit : 1 bit   ▪Data bit : 7 or 8 bit

▪Parity bit : NONE / EVEN / ODD ▪Stop bit : 1 or 2 bit

Protocol

▪PC-LINK STD ▪PC-LINK WITH SUM ▪MODBUS-ASCII ▪MODBUS-RTU

Response

time

Actual response time = processing time + (response time X 50 ms)

Power

AC Power Supply

Voltage

100 - 240 V a.c., 50/60 Hz

DC Power Supply

Voltage

24 V d.c., Class2

Voltage fluctuation

rate

± 10 % of power voltage

Insulation

resistance

Min. 20 MΩ, 500 V d.c.

Dielectric

strength

▪3,000 V a.c.

▪50/60 Hz for 1 minute (between 1st and 2nd terminal)

AC voltage type

power consumption

Max. 8.5 VA

Max. 8.5 VA

Max. 8.2 VA

Max. 8.5 VA

Max. 9.0 VA

DC voltage type

power consumption

Max. 2.7 W

Max. 2.7 W

Max. 2 W

Max. 2.8 W

Max. 3.2 W

Ambient temperature

& humidity

-10 ~ 50 ℃, 35 ~ 85 % RH (without condensation)

Storage temperature

-25 ~ 65 ℃

Certification

CE-KC-RU ROHS2

▪Electrostatic discharge (ESD) : KN61000-4-2   ▪EFT(RS) : KN61000-4-3

▪Conductive RF (CS) : KN61000-4-6   ▪SURGE : KN61000-4-5

IP65 (front panel)

IP65 (front panel)

IP66 (front panel)

IP65 (front panel)

IP65 (front panel)

Weight

202 g

202 g

120 g

194 g

290 g

Basic components

Main body, Bracket, 250 Ω resistor (1%) , Rubber packing, Instruction manual

▍Suffix code

Model

Code

Content

VX

- -

LCD Digital Temperature Controller

Size

2

48(W) x 96(H) x 62.5(D) ㎜

3

96(W) x 48(H) x 62.5(D) ㎜

4

48(W) x 48(H) x 63(D) ㎜

7

72(W) x 72(H) x 62.5(D) ㎜

9

96(W) x 96(H) x 62.5(D) ㎜

Sensor

U

Universal input

OUT 1

(control output 1)

M

Relay output

S

Voltage pulse output (voltage pulse output for SSR drive)

C

Current output (4-20 mA current output for SCR drive)

OUT 2

(control output 2)

N

None

M

Relay output

Power

A

100 - 240 V a.c., 50/60 Hz

D

24 V d.c., Class2

Sub output

A1

1 relay output (VX4 basic option)

A2

2 relay outputs (VX2, VX7, VX9 basic option)

A4

4 relay outputs (※ *1)

Communication

C

RS-485 communication

Retransmission output (RET)

T

Retransmission output (4 ~ 20 mA)

Digital input (DI)

D2

2 digital inputs (DI 1 ~ 2)

Current detection input (CT)

H1

Current detection input (CT) 1 contact

Remote input (REM)

R

1 input, 4 ~ 20 mA (1 ~ 5 V)

※ * 1) ou can choose from VX2, VX3, VX7, and VX9 except for VX4.

▍Dimension and panel cutout

■ Dimension

Dimension

[Unit : ㎜]

Classification

Type

VX2

VX3

VX4

VX7

VX9

Product

dimensions

W

48.0

96.0

48.0

72.0

96.0

H

96.0

48.0

48.0

72.0

96.0

D

62.5

62.5

63.0

62.5

62.5

D1

5.5

5.5

5.0

5.5

5.5

L

78.4

78.4

78.4

78.4

78.4

■ Panel cutout

Panel cutout

[Unit : ㎜]

Classification

Type

VX2

VX3

VX4

VX7

VX9

Panel

cutout

H1

*1)

45.0

90.5

45.0

67.5

92.0

H1

*1)

90.5

45.0

45.0

67.5

92.0

A

70.0

122.0

60.0

83.0

117.0

B *2)

122.0

70.0

60.0

100.0

117.0

* 1) +0.5 mm tolerance applied

* 2) 100.0 mm applied when using USB Loader cable in VX4

■ Protective cover dimensions

Protective cover dimensions
[Unit : ㎜]

Classification

Type

TC2A-COV

TC4A-COV

TC7A-COV

TC9A-COV

Protective

cover

W2

48.4

94.4

48.0

71.8

96.0

H2

94.4

48.4

48.1

71.8

96.0

D2

26.9

26.9

24.0

26.9

26.9